Areas of application
 |
Roofs with a pitch from 3° to vertical. |
 |
Classes of internal humidity load: 1 to 4. |
 |
Both renovations and new buildings. |
VM ZINC®, the choices
|
 |
|
Characteristics of this technique
 |
VM ZINC® is installed on the roof boarding. |
 |
A 40 mm continuous air gap must be left clear beneath the roof boarding, on all the roof pitches. |
 |
Continuous ventilation openings are made at the top and bottom. |
 |
In order to keep the integrity of the roof, it is recommended to install a breather membrane on the cold side of the insulation and a vapour control layer adapted to the internal humidity load of the building, on the warm side of the insulation. |
Structure
 |
Clean and dry 100 to 150 mm wide, 18 or 24 mm thick softwood boarding, according to the rafter centres. |
 |
Any wood treatment products (fungicides, insecticides) must be dry and completely neutral in relation to VM ZINC®. |
 |
The roof boards are fixed perpendicular to the direction of the pitch leaving a 3 to 5 mm gap between them. They are securely fixed to the structure. |
 |
Maximum difference in height of 1 mm between roof boards. The deflection measured under a rigid 600 mm long straight edge cannot exceed 2 mm in all directions. |
 |
The roof board nails are countersunk in order to avoid any contact with the VM ZINC®. |
 |
In case of incompatible support (e.g. plywood), one should use only VM ZINC® PLUS. |
|
|
|